Over-Heat Dump Zones for Solid Fuel Hot Water Boilers

All Solid fuel hot water boilers must be installed with an ability to shed heat with or without the benefit of electrical power. In the unusual event a boiler exceeds its set-point temperature and the temperature is continuing to climb, an over-heat dump zone may be the only means for preventing the boiler from making […]
Simplified Pipe/Pump Sizing Chart (Copper Tubing)
Copper Pipe & Pump Sizing Pipe Size BTUH Friction Head Feet 100’ (straight pipe) Friction Head Feet 100’ (allowance for fittings and boiler) Gallons per Minute (GPM) at 20 degree Delta T 1/2” 17,000 4.2’ 6’ 1.7 3/4” 39,000 4.2’ 6’ 3.9 1” 71,000 4.2’ 6’ 7.1 1-1/4” 160,000 4.2’ 6’ 16.0 1-1/2” 240,000 4.2’ […]
Multi-Heat Programming, Start-up, and Cleaning Videos
Below is a step by step video for programming the Multi-Heat Pellet Boiler. Multi-Heat Programming Video Below is a step by step video for starting and cleaning the Multi-Heat boiler. Multi-heat Starting and Cleaning
How to Buy PEX Pipe Systems for Remote Building or Outdoor Boiler Installation
What is PEX Pipe? PEX is an acronym for Cross Linked Polyethylene. It is a relatively hard plastic, which is somewhat flexible in longer lengths. PEX pipe is very strong, smooth-walled, and can generally withstand fluid temperatures up to 180 degrees Fahrenheit without significant loss of strength. Most PEX pipe made for heating applications […]